Quantity |
: 1 pce
|
Application |
: Power Transformer
|
Basic Transformer Concept |
: oil-immersed, conservator tank
|
Tank Design |
: Rigid tank, detachable cooling radiators
|
Number of Phases |
: 3-phase
|
Winding Material |
: Cu/Cu
|
Insulation Liquid |
: Inhibited Mineral Oil
|
Rated Power |
: 30000 / 50000 kVA
|
Method of Cooling |
: ONAN/ONAF
|
Voltage Ratio |
: 110000 / 23000 / 6300 V
|
Tapping Range |
: +-8x2%
|
Type of Regulation |
: OLTC - On-load Tap Changer
|
Brand and Type of OLTC |
: MR Vacutap VV
|
Frequency |
: 50 Hz
|
Temperature Rise |
: 60/65 K
|
Impedance |
: 11,5%
|
No-Load Losses |
: 22000 W
|
Load Losses |
: 140000 W
|
Connection |
: YNyn0(d)
|
Standards |
: IEC 60076
|
Total Weight |
: ~72800 kg
|
Weight of Oil |
: ~14200 kg
|
Appr. Dimensions (LxWxH) |
: 6030x3200x4980 mm
|
Transport Dimensions |
: 5750x2100x3810 mm
|
|
Regulation Range of OLTC |
:
|
|
|
127600 V
|
125400 V
|
123200 V
|
121000 V
|
118800 V
|
116600 V
|
114400 V
|
112200 V
|
110000 V
|
107800 V
|
105600 V
|
103400 V
|
101200 V
|
99000 V
|
96800 V
|
94600 V
|
92400 V |