#69 - 6 MVA 20/6.3 kV
Quantity | : 1 pce |
Year of Manufacture | : 2011 |
Make | : TBA |
Basic Design | : Oil-immersed |
Number of Phases | : Three-phase |
Application | : Power Transformer |
Rated Power | : 6000 kVA |
Method of Cooling | : ONAN |
Voltage Ratio | : 20000 / 6300 V |
Tappings Range | : +-2x2,5% |
Type of Tap changer | : Off-circuit Tap Changer |
Vector Group | : Dyn11 |
Frequency | : 50 Hz |
Short Circuit Voltage | : 6,92 % |
Temperature Rise | : 60/65 K |
No-load Losses | : 6450 W |
Load Losses at 75 °C | : 44 375 W |
Conductor Material (HV/LV) | : Cu/Cu |
Place of Installation | : Outdoor |
Outer Dimensions (LxWxH) | : 2330x2050x2780 mm |
Total Weight | : 9500 kg |
Weight of Oil | : 2000 kg |
Standards | : IEC 60076 |