Quantity |
: 1 pce
|
Application |
: Power Transformer (Generator Transformer)
|
Basic Transformer Concept |
: oil-immersed, conservator tank
|
Tank Design |
: Rigid tank, detachable cooling radiators
|
Number of Phases |
: 3-phase
|
Rated Power |
: 70000/85000/100000 kVA
|
Method of Cooling |
: ONAN/ONAF
|
Voltage Ratio |
: 220000 / 33000 V
|
Tapping Range |
: +-8x1.25%
|
Type of Tap Changer |
: OLTC - On-load Tap Changer
|
Frequency |
: 50 Hz
|
Temperature Rise |
: 50/55 K
|
Connection |
: YNyn0
|
Standards |
: IEC 60076
|
Total Weight |
: ~130 000 kg
|
Weight of Oil |
: ~38 200 kg
|
|
Regulation Range of OLTC |
:
|
|
|
: Pos. 1 - 242000 V
|
|
: Pos. 2 - 239250 V
|
|
: Pos. 3 - 236500 V
|
|
: Pos. 4 - 233750 V
|
|
: Pos. 5 - 231000 V
|
|
: Pos. 6 - 228250 V
|
|
: Pos. 7 - 225500 V
|
|
: Pos. 8 - 222750 V
|
|
: Pos. 9 - 220000 V
|
|
: Pos.10 - 217250 V
|
|
: Pos.11 - 214500 V
|
|
: Pos.12 - 211750 V
|
|
: Pos.13 - 209000 V
|
|
: Pos.14 - 206250 V
|
|
: Pos.15 - 203500 V
|
|
: Pos.16 - 200750 V
|
|
: Pos.17 - 198000 V |