Quantity |
: 1 pce
|
Brand |
: ABB
|
Year of Manufacture |
: 2012
|
Condition |
: Surplus, unused
|
Application |
: Power Transformer
|
Basic Transformer Concept |
: Oil-immersed, conservator tank
|
Tank Design |
: Rigid tank, detachable cooling radiators
|
Number of Phases |
: 3-phase
|
Rated Power |
: 18 000 kVA / 25 000 kVA
|
Method of Cooling |
: ONAN / ONAF
|
Voltage Ratio (prim./sec.) |
: 110 000/ 20 000 V
|
Voltage Regulation |
: On-load tap changer (OLTC)
|
Tapping Range |
: +-9 x 1,78%V (see table below)
|
Frequency |
: 50 Hz
|
Temperature Rise |
: 60/65K
|
Connection |
: YNd11
|
|
Total Weight |
: ~36 500 kg
|
Weight of Oil |
: ~10 300 kg
|
Transport Weight |
: ~34 600 kg
|
|
Table of tappings |
:
|
|
-9 92 378 / 20 000 V
|
-8 94 336 / 20 000 V
|
-7 96 294 / 20 000 V
|
-6 98 252 / 20 000 V
|
-5 100 210 / 20 000 V
|
-4 102 168 / 20 000 V
|
-3 104 126 / 20 000 V
|
-2 106 084 / 20 000 V
|
-1 108 042 / 20 000 V
|
0 110 000 / 20 000 V
|
1 111 958 / 20 000 V
|
2 113 916 / 20 000 V
|
3 115 874 / 20 000 V
|
4 117 832 / 20 000 V
|
5 119 790 / 20 000 V
|
6 121 748 / 20 000 V
|
7 123 706 / 20 000 V
|
8 125 664 / 20 000 V
|
9 127 622 / 20 000 V
|
|
|
|
|
Further documentation is available upon request! |