Losses according to new Eco Design requirements!
|
|
Brand |
: BTB Trafo, HPS Italy
|
Year of Manufacture |
: 2015
|
Condition |
: New Unused
|
Basic Transformer Design |
: Cast Resin
|
Ingress Protection |
: IP00
|
Classifications |
: C2 - E2 - F1
|
Application |
: Distribution Transformer, Dual Voltage
|
Number of Phases |
: Three-phase
|
Rated Power |
: 1000 kVA
|
Cooling |
: AN
|
Voltage Ratio |
: 20 000 (10 000)/ 400 V
|
Prim .Ins. Level (Um/LI/AC) |
: 24 kV / LI 95/ AC 50
|
Sec. Ins. Level (Um/LI/AC) |
: 1,1 kV / - / AC 3
|
Voltage Regulation |
: off-circuit, bolted links
|
Tapping Range |
: +-2x2.5%, see table below
|
Temperature Class (HV/LV) |
: Class F / Class F
|
Temperature Rise (HV/LV) |
: 100/100 K
|
Frequency |
: 50 Hz
|
Vector Group |
: D(D)yn11
|
Standards |
: IEC 60076-11
|
Impedance |
: 6 %
|
Total Weigth |
: 3352 kg
|
|
|
Tapping, Voltage (Dual Voltage)
|
|
2 21 000 V (10 500)
|
1 22 500 V (10 250)
|
0 20 000 V (10 000)
|
-1 19 500 V (9 750)
|
-2 19 000 V (9 500) |