Quantity |
: 1 pce
|
Brand |
: GEC Alsthom, France
|
Year of Manufacture |
: 1991
|
Condition |
: Second Hand
|
Application |
: Power Transformer
|
Basic Transformer Concept |
: Oil-immersed, conservator tank
|
Tank Design |
: Rigid tank, detachable cooling radiators
|
Number of Phases |
: 3-phase
|
Rated Power |
: 47000 kVA
|
Method of Cooling |
: ONAN/ONAF - 68/100%
|
Voltage Ratio (prim./sec.) |
: 33000 / 10500 V
|
Primary Current |
: 822 A
|
Secondary Current |
: 2584 A
|
Voltage Regulation |
: On-load tap changer (OLTC)
|
Tapping Range |
: +-10%, see table below for tapping range
|
Frequency |
: 50 Hz
|
Connection |
: YNd11
|
Impedance |
: 12% at 47 MVA
|
Temperature Rise (oil/wind) |
: 50/55 K
|
Standards |
: C.E.I - V.D.E
|
|
Total Weight |
: ~52300 kg
|
Weight of Oil |
: ~12700 kg
|
|
Further documentation is available and can be sent upon request!
|
|
Tapping Range |
:
|
|
1. 36300/10500 V
|
2. 35880/10500 V
|
3. 35475/10500 V
|
4. 35063/10500 V
|
5. 34650/10500 V
|
6. 34238/10500 V
|
7. 33825/10500 V
|
8. 33413/10500 V
|
9. 33000/10500 V
|
10. 32588/10500 V
|
11. 32175/10500 V
|
12. 31763/10500 V
|
13. 31350/10500 V
|
14. 30936/10500 V
|
15. 30525/10500 V
|
16. 30113/10500 V
|
17. 29700/10500 V |